Fire Science and Technology ›› 2020, Vol. 39 ›› Issue (6): 768-771.
Previous Articles Next Articles
WANG Hai-tao, LI Bin, CAO Hui-juan, FENG Dao-guang
Received:
Online:
Published:
Abstract: A hot smoke test was carried out in a real subway tunnel to verify the validity of FDS simulation results. Three- dimension model of subway tunnel was established and effects of outdoor air design parameters on smoke back- layering length and critical velocity were investigated by FDS. Results of study showed that outdoor air design parameters have important influences on smoke back-layering length in subway tunnel fires. The smoke back-layering is longer when the design temperature of outdoor air is lower. The smoke back-layering is shorter when outdoor air design humidity is bigger. The smoke back- layering is shorter when outdoor atmospheric pressure is bigger.
Key words: outdoor air, air temperature, atmospheric pressure, air humidity, smoke back- layering flow, back- layering length, critical velocity
CLC Number:
X913.4,TU834.2,U459.3
WANG Hai-tao, LI Bin, CAO Hui-juan, FENG Dao-guang. Effects of outdoor air on smoke back-layering length in subway tunnel[J]. Fire Science and Technology, 2020, 39(6): 768-771.