主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2020, Vol. 39 ›› Issue (8): 1124-1127.

Previous Articles     Next Articles

Effectiveness evaluation of transformer fire extinguishing system of UHV converter station based on simulation experiments

WANG Shou-jiang1,CHEN Qin-pei2   

  1. 1. Xinjiang Fire and Rescue Brigade, Xinjiang Urumqi 830000,China;2. Tianjin Fire Science and Technolgy Research Institute of MEM,Tianjin 300381,China
  • Online:2020-08-15 Published:2020-08-15

Abstract: In order to build an effective UHV converter station transformer automatic fire protection system, a comprehensive analysis of the characteristics of this type of transformer fire is carried out, and based on the method of solid fire simulation experiments, the effectiveness of the high- pressure water mist system and the water mist turbofan gun system for fire extinguishing is emphasized. The experimental results show that both systems have efficient fire extinguishing performance, and the lateral sprinkler can effectively improve the fire extinguishing efficiency of the highpressure water mist system;The sequence of fire extinguishing actions of the turbofan gun system should be from top to bottom, and continuous cooling after spraying to prevent reignition .

Key words: converter station, high- pressure water mist system, turbofan gun water mist system