主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2021, Vol. 40 ›› Issue (6): 855-860.

Previous Articles     Next Articles

Numerical simulation study on fire development law of outdoor composite soft oil sac

WANG Chun-hui, JIANG Xin-sheng, ZHANG Lin, YU Bin-bin, CAI Yun-xiong, WANG Zi-tuo, HE Dong-hai   

  1. Department of Oil, Army Logistics Academy of PLA, Chongqing 401331, China
  • Online:2021-06-15 Published:2021-06-15

Abstract: According to the combustion characteristics of oil fire, FLACS software was used to simulate the combustion process of small scale 0.5 m oil pool fire and the leakage and fire process of large scale field combined soft oil sac. The results show that: the distribution of maximum heat radiation flux of oil pool fire combustion is not strictly symmetrical with the central axis of oil pool. In the process of flowing fire combustion after oil leakage of the outdoor combined oil sac, the maximum radiation intensity received by the whole self- loading pallet is up to 35 kW/m2, and the maximum radiation intensity received by the oil sac is about 18 kW/m2. 20 seconds after the oil fire occurs, the thermal radiation intensity of the oil sac can reach the minimum energy for oil sac melting.

Key words: oil fire, thermal radiation, FLACS, numerical simulation, oil sac