主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2020, Vol. 39 ›› Issue (10): 1418-1420.

Previous Articles     Next Articles

Experimental study on the ignition condition of EPS external insulation material by gasoline torch

CHENG Zhi-ran   

  1. Yantai Fire and Rescue Division, Shandong Yantai 264003, China
  • Online:2020-10-15 Published:2020-10-15

Abstract: The gasoline torch was used to ignite the ordinary and flame- retardant EPS external insulation material under different distances. The results showed that the two types of EPS could be ignited when they directly contacted to the gasoline torch flame.The surface of EPS only got different degrees of shrinkage and melting when there was a distance between the EPS and the gasoline torch flame, and the material was not ignited. The further the distance was, the smaller the shrinkage range was and the less the melting degree was.

Key words: EPS, gasoline torch, ignition condition