Experimental study on extinguishing wholesurface spill fire of transformers by compressed air foam

HU Cheng 1 , CHEN Tao 1 ,FU Xue - cheng 1 , ZHAO Li - zeng 1 , ZHANG Jia - qing 2 , HUANG Yong 3   

  1. (1.Tianjin Fire Science and Technology Research Institute of MEM,Tianjin 300381, China; 2.State Grid Anhui Electric Power Research Institute, Anhui Hefei 230601, China; 3. State Grid Economic and Technology Research Institute Co., Ltd., Beijing 102209, China)
  • Received:2020-02-24 Online:2020-07-15 Published:2020-07-15

Abstract: Based on causes of oil spill fires in transformers,a series of small - scale experiments on compressed air foam extinguishing whole - surface spill fires in transformers were studied.With compressed air foam sprinkler system and foam gun,two types of fire extinguishing methods were applied.The advantage and variation rule of extinguishing whole - surface oil spill fires in transformers with compressed air foam were evaluated. The study showed that the film - formed compressed air foam was effective in extinguishing whole - surface oil spill fires in transformers.It could form a stable coating on the high - temperature oil surface to prevent boiling and splashing.Cooling was the key factor for extinguishing fire.It could extinguish whole - surface oil spill fires in transformers and prevent re - ignition by cooling the oil temperature below the ignition point.

Key words: oil - immersed transformer;whole - surface, compressed air foam;spill fire