主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2020, Vol. 39 ›› Issue (9): 1277-1279.

Previous Articles     Next Articles

Study on the generation of hydrogen fluoride by thermal decomposition of C6F-ketone extinguishing agent

CHEN Pei-yao,ZHUANG Shuang,LIU Qi,LI Shu,LIU Hui-min   

  1. Tianjin Fire Science and Technology Research Institute of MEM,Tianjin 300381, China)
  • Online:2020-09-15 Published:2020-09-15

Abstract: Pyrolysis behaviors of C6F-ketone were simulated using a tube cracking furnace and the factors influence HF generation were studied. HF generation by C6F- ketone extinguishing agents from different production processes were compared, then HF generation was compared with C6F-ketone and other HFCs. The share of HF generated from thermal decomposition increased with decomposition temperature and residence time. The HF generation of C6F-ketone from differnt production technology were mostly the same. Compared with other HFCs, initial cracking temperature of C6F- ketone was lower(500 ℃ ), more HF was generated at low and moderate temperatures(550~750 ℃).

Key words: C6F-ketone, thermal decomposition, hydrogen fluoride