主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2023, Vol. 42 ›› Issue (11): 1457-1461.

    Next Articles

Research on fire fighting technology for UHV converter transformer based on lifting and spraying fire extinguishing robot

Chen Tao1,2,3, Zhang Peng1,2,3, Zhang Jiaqing4, Wang Yuwei1,2,3   

  1. (1. Tianjin Fire Science and Technology Research Institute of MEM,Tianjin 300381,China; 2. Key Laboratory of Fire Protection Technology for Industry and Public Building, Ministry of Emergency Management, Tianjin 300381, China; 3. Tianjin Key Laboratory of Fire Safety Technology, Tianjin 300381, China; 4. State Grid Anhui Electric Power Research Institute, Anhui Hefei 230601, China)
  • Online:2023-11-15 Published:2023-11-15

Abstract: In order to explore the effectiveness of compressed air foam aerial fire fighting robot in dealing with oil immersed transformer fires, this paper developed a 1:1 full-scale oil immersed transformer fire model, simulated the oil pool fire at the top of the main oil tank, 7 combustion holes, oil spill fire and bottom oil pool fire, and conducted a full-scale oil immersed transformer fire suppression test using a compressed air foam aerial fire fighting robot. The result shows that a compressed air foam aerial fire fighting robot with a flow rate of 1 200 L/min can extinguish the fire of full-scale oil immersed transformer, control the fire in 163 s, and completely extinguish the fire in 474 s without re burning.

Key words: oil immersed transformer, fire model, compressed air foam, aerial fire fighting robot, extinguishing technology