主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2022, Vol. 41 ›› Issue (10): 1435-1439.

Previous Articles     Next Articles

Experimental study on extinguishing full-level oil spill fire of UHVDC converter transformer by compressed air foam

Chen Tao1, Zhang Jiaqing2, Jing Lishuai1, Hong Qingquan3   

  1. (1. Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China; 2. State Grid Anhui Electric Power Research Institute, Anhui Hefei 230601, China; 3.GuoAnda Co., Ltd., Fujian Xiamen, China)
  • Online:2022-10-15 Published:2022-10-15

Abstract: Abstract: The combustion experiments of outdoor multiple fires and single pool fire were carried out under different pool diameter (1.0, 1.4, 1.7 m) and different pool spacing (1.5D, 1.75D, 2D). In the experiment, camera, electronic balance andthermocouples were used to monitor the flame height, the burning rate and the flame temperature respectively. Results show that the burning rate of each fire in the multiple-fire experiments is higher than that of a single pool fire with the same diameter, and when the flame mergence occurs at the distance of 1.5D, the merging flame height is higher than single pool fire flame height with the same diameter, indicating that the combustion risk of multiple-fire is greater. In addition, after the four flames mergence, the exponential changes of flame temperature at the geometric central axis with height are 0.13, [-1.02] and [-1.46], which is basically consistent with the recognized central axis temperature change of common buoyant pool fire, which indicates that multiple flames merge into a common buoyant pool fire.

Key words: Key words: outdoor multiple fires, burning rate, flame temperature, flame height, experimental study