主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2022, Vol. 41 ›› Issue (10): 1376-1379.

Previous Articles     Next Articles

Study on toxicity evaluation of fire effluents based on bench-scale and middle-scale smoke generation model

Deng Xiaobing, Li Xili, Zhu Jian   

  1. (Sichuan Fire Science and Technology Research Institute of MEM, Sichuan Chengdu 611830, China)
  • Online:2022-10-15 Published:2022-10-15

Abstract: Abstract: To improve the applicability of fiber optic sensors in building fire warning, this study conducts high temperature experiments on single-mode and multi-mode fiber optic sensors based on fire temperature rise curve, and analyzes their temperature sensing performance, and then selects the sensor whose temperature sensing performance suits building fire better. Based on the experimental data, a temperature rise error correction model was established to improve the temperature measurement accuracy. The results show that the multimode fiber optic sensor is much better than the single-mode fiber optic sensor in terms of temperature measurement stability, and has more correction value. The temperature rise error correction model built can lower the temperature measurement mean absolute error to 13.12 ℃. Using distributed optical fiber to draw high-precision building fire map has become the technical key of fire monitoring and early warning, evacuation and rescue, and structural collapse prediction.

Key words: Key words: distributed optical fiber, fire empirical model, temperature sensing performance, heating curve, curve fitting