主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2022, Vol. 41 ›› Issue (7): 873-876.

    Next Articles

Experimental study on extinguishing efficiency of 2-BTP on battery fires

XU Hui-sheng, CONG Xiao-min, ZHAO Lin-shuang, WANG Xi   

  1. (College of Mechanical and Electrical Engineering, Beijing Institute of Technology, Beijing 100081, China)
  • Online:2022-07-15 Published:2022-07-15

Abstract: Abstract: A set of fire extinguishing experimental platform was set up, the rated capacity of 75 Ah ternary flexible lithium-ion battery was taken as the research object . A constant power of 1 000 W aluminum casting heating plate was used to induce thermal loss of the battery. The combustion characteristics of the battery under 50% SOC were analyzed, and the effect of 2-BTP on battery fire suppression and cooling was studied.?Compared with water, FM-200 and HFC-125 under equal working conditions, the fire extinguishing time, maximum temperature and re-ignition of different extinguishing agents were analyzed.?The experimental results show that under the set conditions, 2-BTP is the fastest to extinguish the flame within 13 s. 2-BTP not only has the fastest fire-extinguishing speed and the best cooling effect, but also can effectively inhibit the re-ignition of lithium ion battery.

Key words: Key words: 2-BTP, lithium-ion battery, combustion characteristic, fire extinguishing efficiency