主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2021, Vol. 40 ›› Issue (8): 1225-1227.

Previous Articles     Next Articles

Study on the influence of chemical components on the filling performance of dry water fire extinguishing agent

KONG Ling-dong1,2, SHI Hong-xing1,2, ZHANG Tong1,2, LIU Xiang-cui1,2   

  1. 1.Academy of Military Sciences PLA China, Institute of Chemical Defense, Beijing 102205, China; 2. State Key Laboratory of NBC Protection for Civilian, Beijing 102205, China
  • Online:2021-08-15 Published:2021-03-15

Abstract:

A series of dry water fire extinguishing agents coated with functional chemical fire extinguishing components are designed and prepared, and the effects of different functional chemical fire extinguishing components on the bulk density and structural stability of dry water fire extinguishing agents under high pressure are studied. The results show that the bulk density of dry water fire extinguishing agent is 0.348 0 ~ 0.437 3 g/mL; dry water fire extinguishing agent below 150 μm has better pressure resistance; the addition of different fire extinguishing components has no obvious influence on the pressure resistance, but the addition of gelling agent can significantly improve the structural stability of the dry water fire extinguishing agent, so that it can maintain the original stable structure under high pressure. The research results are of great significance to the promotion and use of dry water extinguishing agents.

Key words: dry water, fire extinguishing agent, fire extinguishing component, bulk density, pressure resistance