主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

消防科学与技术 ›› 2020, Vol. 39 ›› Issue (11): 1561-1564.

• • 上一篇    下一篇

基于NB-IoT 的消火栓状态实时监测方法研究

吴津津1,2,毛家润3,袁宏永1,疏学明1   

  1. 1. 清华大学公共安全研究院,北京100084;2. 北京辰安科技股份有限公司,北京100084;3. 深圳市龙华区应急管理局,广东深圳518110
  • 出版日期:2020-11-15 发布日期:2020-11-15
  • 通讯作者: 疏学明,清华大学公共安全研究院副教授。
  • 作者简介:吴津津(1992-),男,天津人,北京辰安科技股份有限公司助理工程师,硕士,主要从事消防、风险评估方面的研究,北京市海淀区双清大厦3 号楼11 层,100084。
  • 基金资助:
    国家重点研发计划项目(2017YFC0806600)

Study on real-time monitoring method of fire hydrant status based on NB-IoT

WU Jin-jin1,2, MAO Jia-run3, YUAN Hong-yong1, SHU Xue-ming1   

  1. 1. Institute of Public Safety Research, Tsinghua University,Beijing 100084, China;2. Beijing GS Technology Co., Ltd.,Beijing 100084, China;3. Emergency Management Bureau of Longhua District, Guangdong Shenzhen 518110, China
  • Online:2020-11-15 Published:2020-11-15

摘要: 为了实现对消火栓状态的实时监测,掌握其水压、流量、温度的数据信息,研制了消火栓监测仪,对数据传输信号强度与消火栓状态实时监测方法进行分析与研究。分析基于NBIoT网络传输的消火栓监测仪在多种空间情形下的信号强度。对市政消火栓进行实时监测,从动压与静压两方面分析其水压变化趋势。分析阀门状态、探测周期对流量监测的影响。结合当地气温验证供水管网内水源温度监测的准确性。实验结果表明:消火栓监测仪数据传输可靠,压力在0~400 kPa 范围内监测准确、流量在0.2~25 L/s 范围内测量灵敏、温度监测数据与当地气温相符,满足消火栓状态实时监测需求。

关键词: 消防, 消火栓, 无线通信, 实时监测

Abstract:

In order to monitor the real-time status of water pressure,flow and temperature of fire hydrants, a fire hydrant monitor is developed, and signal strength of data transmission and real-time monitoring methods of fire hydrant status are analyzed and studied. Firstly, analyze the signal strength of the hydrant monitor based on NB-IoT network transmission in various space situations. Secondly, the real- time monitoring of a municipal fire hydrant is carried out, and its water pressure change trend is analyzed from both dynamic pressure and static pressure. Then,the effects of valve status and detection cycle on flow monitoring are analyzed. Finally, combined with local temperature, the accuracy of temperature monitoring in the water supply pipe is verified. The results show that the data transmission of the fire hydrant monitor is reliable, the pressure is accurately monitored in the range of 0~400 kPa, the flow rate is sensitively measured in the range of 0.2~25 L/s, and the temperature monitoring data is consistent with local temperature. The results meet the needs of fire hydrant monitoring.

Key words:

fire protection, fire hydrant monitoring, wireless communication, real-time monitoring