摘要: 为研究导线在过负荷状态下的发热和引燃特性,利用实验台模拟不同环境条件,对不同材质和截面积的导体,在无可燃物和周围有碎纸和棉花的条件下,进行了试验研究。结果表明,导线在周围有无可燃物的时候,温升曲线均符合单指数函数变化趋势,最终平衡温度总体上对应过负荷倍数分为4 或5 个阶段,1.5 mm2 铜导线的温度均高于同条件下其他导线。在无可燃物时,拟合函数的参数与过负荷电流倍数呈线性关系;在有可燃物时,则成二次多项式和三次多项式关系。在有可燃物时,同条件下导线的最后温升均高于无可燃物条件,除1.5 mm2 铜导线因为引燃纸屑而温度最高外,其余均为4Ie 下棉花包裹时温度最高,棉花最终均未明火燃烧,仅出现阴燃现象。研究结论可以为过负荷类电气火灾的预防和火场复原以及火灾调查提供参考。

关键词: 过负荷, 导线, 发热特性, 引燃能力

Abstract: Using the experimental platform, the thermal characteristics and ignition capability of wires with different materials and cross-sectional areas under overload were studied under the conditions with or without of combustibles such as scrap paper and cotton. The results show that the temperature rise curve of the wire conforms to the trend of single exponential function in all cases. All final temperature values of the wire are generally divided into 4 or 5 stages corresponding to overload multiples.Copper wires with a cross- sectional area of 1.5 mm2 have the highest temperature. The relation between parameters of the fitting function of the wire temperature rise curve and the overload current multiple is linear when there is no combustible,and is quadratic or cubic polynomial when there is combustible.Under the same conditions, the final temperature of the wire is higher when there is combustible material. Except that the copper wire with a cross- sectional area of 1.5 mm2 had the highest temperature due to paper burning, the temperature of the other wire wrapped by cotton was relatively high under 4 Ie. Until the end of the experiment, cotton was only smoldering. The conclusions of this study can provide reference for the prevention and recovery of overload electrical fire and fire investigation.

Key words: overload, electric wire, heating characteristics, ignition capacity