机场塔台无高位消防水箱之增强措施探讨

衣兰凯1,赵乐乐1,叶超2,连震雷1,朱其原1   

  1. 1. 民航机场规划设计研究总院有限公司,北京100101;2. 国家消防工程技术研究中心,天津300382
  • 收稿日期:2019-08-25 出版日期:2020-01-15 发布日期:2020-01-15
  • 作者简介:衣兰凯(1985-),男,北京人,民航机场规划设计研究总院有限公司高级工程师,主要从事机场给排水及消防规划设计研究,北京市朝阳区惠新东街甲2 号住总地产大厦,100101。

Discussion about strengthening measures for an airport tower without elevated fire tank

YI Lan-kai1,ZHAO Le-le1,YE Chao2,LIAN Zhen-lei1,ZHU Qi-yuan1   

  1. 1. China Airport Planning & Design Institute Co.,Ltd.,Beijing 100101,China;2. National Center for Fire Engineering Technology, Tianjin 300382,China
  • Received:2019-08-25 Online:2020-01-15 Published:2020-01-15

摘要: 机场塔台顶层指挥明室因空管工艺需求,屋顶采用轻钢结构,受结构承载力和限高的要求,塔台无法设置高位消防水箱。通过火灾场景、烟气流动模拟和人员安全疏散分析,提出消防强化措施,主要包括采用稳高压消防系统、两路供水、两路供电、采用快速响应喷头、优化管材选择、采用物联网消防设备和配置空气呼吸机等。模拟结果显示,在发生火灾区域的自动灭火系统和排烟系统有效的情况下,清晰高度处的人员可用疏散时间较长,该消防方案能达到防止火灾大规模蔓延和保障建筑内人员安全的消防设计安全目标。

关键词: 机场塔台, 高位消防水箱, 安全疏散, 稳高压系统, 自动灭火系统

Abstract: Due to the requirements of the tower command dimroom, the roof adopts light steel structure. The tower cannot set elevated fire tank restricted by bearing capacity of structure and building height. Analyzing fire scene, fire smoke flow and personnel safe evacuation, strengthening measures were proposed, such as fire water supply system of stable-high pressure, two way of water supply,dual power supply, using fast response sprinkler optimizing the selection of pipes, firefighting equipment with internet
of things, and deploying air ventilator. Evacuation time was long in the event that the automatic fire extinguishing system and smoke exhaust system in the fire area were effective, achieving the design safety goal which can prevent fire from spreading in large scale andguarantee the personnel safety in the building.

Key words: airport tower, elevated fire tank, safe evacuation, fire water supply system of stable- high pressure, automatic fire distinguish system