主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

消防科学与技术 ›› 2022, Vol. 41 ›› Issue (1): 100-103.

• • 上一篇    下一篇

模块化数据中心感烟灭火装置优化设计

刘建翔1,2,李 宗1,赵志鹏1,2,李绍鹏1,2   

  1. (1.齐鲁工业大学(山东省科学院),山东 济南 250014;2.山东省科学院 自动化研究所,山东 济南 250014)
  • 出版日期:2022-01-15 发布日期:2022-01-15
  • 作者简介:刘建翔(1977-),男,山东昌邑人,山东省科学院自动化研究所研究员,博士,硕士生导师,主要从事智能检测与控制方面的研究,山东省济南市历下区科院路19号,250014。

Optimal design of smoke fire extinguishing device in modular data center

LIU Jian-xiang1,2, LI Zong1,ZHAO Zhi-peng1,2, LI Shao-peng1,2   

  1. (1. Qilu University of Technology (Shandong Academy of Sciences), Shandong Ji'nan 250301, China; 2. Institute of Automation, Shandong Academy of Sciences, Shandong Ji'nan 250014, China)
  • Online:2022-01-15 Published:2022-01-15

关键词: 模块化数据中心;感烟探测;全氟己酮;优化设计

Abstract: The paper designs the smoke-sensing fire-extinguishing device for fire detection and extinguishing, aiming at the problems of low sensitivity of fire detection, low efficiency of fire extinguishing medium, and danger in pressure storage design of modular data center. Based on Mie scattering principle, active air sampling smoke detection technology is used for early fire detection. The optical simulation software is used to simulate the optical path of the detection chamber, and the structure of the detection anechoic chamber is optimized. A non-pressure-storing, clean and environment-friendly perfluorohexanone fire extinguishing device was invented. The device has multi-level early warning and alarm design. According to the test, the concentrations of initial, medium and advanced early warning of the device are 0.05 db/m, 0.11 db/m and 0.21 db/m respectively. The smoke sensitivity is class I, the average spraying time of fire extinguishing agent is 7.2 s, and the average extinguishing time is 11.2 s. It has high sensitivity and good fire extinguishing ability, which can ensure the safe operation of data center equipment.

Key words: modular data center; smoke detection; perfluorohexanone; optimal design