化学组分对干水灭火剂充装性能的影响研究

孔令冬1,2,史红星1,2,张 彤1,2,刘香翠1,2   

  1. 1.中国人民解放军军事科学院 防化研究院,北京 102205;2.国民核生化灾害防护国家重点实验室,北京 102205
  • 出版日期:2021-08-15 发布日期:2021-03-15
  • 作者简介:孔令冬(1996-),男,山东济宁人,军事科学院防化研究院硕士研究生,主要从事安全应急材料研究,北京市昌平区阳坊镇中心南街37号院,102205。
  • 基金资助:
    国家重点研发计划项目(2016YFC0801502);军队某重点学科建设项目

Study on the influence of chemical components on the filling performance of dry water fire extinguishing agent

KONG Ling-dong1,2, SHI Hong-xing1,2, ZHANG Tong1,2, LIU Xiang-cui1,2   

  1. 1.Academy of Military Sciences PLA China, Institute of Chemical Defense, Beijing 102205, China; 2. State Key Laboratory of NBC Protection for Civilian, Beijing 102205, China
  • Online:2021-08-15 Published:2021-03-15

摘要: 设计并制备了包覆功能性化学灭火组分的系列干水灭火剂,研究了不同功能性化学灭火组分对干水灭火剂松密度和在高压下结构稳定性的影响。结果表明,干水灭火剂的松密度为0.348 0~0.437 3 g/mL;150 μm以下的干水灭火剂具有较好的耐压性能;不同灭火组分的加入对干水灭火剂颗粒的耐压性能没有明显影响,但凝胶剂的加入能够显著提高干水灭火剂的结构稳定性,使其在高压下保持原有稳定结构。研究结果对干水灭火剂的推广使用具有重要意义。

关键词: 干水, 灭火剂, 灭火组分, 松密度, 耐压性

Abstract:

A series of dry water fire extinguishing agents coated with functional chemical fire extinguishing components are designed and prepared, and the effects of different functional chemical fire extinguishing components on the bulk density and structural stability of dry water fire extinguishing agents under high pressure are studied. The results show that the bulk density of dry water fire extinguishing agent is 0.348 0 ~ 0.437 3 g/mL; dry water fire extinguishing agent below 150 μm has better pressure resistance; the addition of different fire extinguishing components has no obvious influence on the pressure resistance, but the addition of gelling agent can significantly improve the structural stability of the dry water fire extinguishing agent, so that it can maintain the original stable structure under high pressure. The research results are of great significance to the promotion and use of dry water extinguishing agents.

Key words: dry water, fire extinguishing agent, fire extinguishing component, bulk density, pressure resistance